Crude Oil Washing and Tank Cleaning on Oil Tankers
Crude oil washing, water washing and gas-freeing of oil tanker cargo tanks: COW programs, inert gas, slop tanks, load-on-top, ODME limits and ORB entries.
Contents21 sections
Crude oil washing (COW) is the cleaning of an oil tanker’s cargo tanks with the crude oil cargo itself, jetted through fixed washing machines during discharge so that wax and asphaltic sludge go ashore with the cargo instead of staying on board. MARPOL Annex I regulation 33 requires it on every crude oil tanker of 20,000 tonnes deadweight and above delivered after 1 June 1982, regulation 35 governs how it is run, and SOLAS II-2/4.5.5.1.3 makes an inert gas system and fixed machines a condition of using it at all. Tank cleaning is the wider cycle around it: water rinsing, slop tank settling and load-on-top, decanting through the oil discharge monitoring and control system (ODMCS), purging, gas-freeing and entry.
The regulatory text sits in the revised Annex I of the MARPOL Convention adopted by MEPC.117(52) on 15 October 2004 and in force from 1 January 2007, which moved the tanker cargo-area rules, including the former regulation 13B on crude oil washing, into regulations 29 to 36. The design and operating detail sits in the COW Specifications, IMO Resolution A.446(XI), adopted on 15 November 1979 and amended by A.497(XII) in 1981 and A.897(21) in 1999. Industry practice is set out in ISGOTT, the International Safety Guide for Oil Tankers and Terminals published by ICS, OCIMF and IAPH.
Which tankers must fit crude oil washing
MARPOL Annex I regulation 33.1 requires every crude oil tanker of 20,000 dwt and above delivered after 1 June 1982 to be fitted with a cargo tank cleaning system using crude oil washing. Regulation 1 defines a crude oil tanker as an oil tanker “engaged in the trade of carrying crude oil”, and a product carrier as one carrying oil other than crude. The COW mandate follows the trade, not the hull, and a chemical tanker washing noxious liquid residues works to MARPOL Annex II regulation 13 instead.
The “delivered after 1 June 1982” test
The date is a defined term, not a delivery date. Under regulation 1.28.4 a tanker counts as delivered after 1 June 1982 if any one of four limbs is met:
- the building contract was placed after 1 June 1979;
- in the absence of a contract, the keel was laid after 1 January 1980;
- delivery took place after 1 June 1982; or
- a major conversion meets the same contract, construction or completion dates.
Every crude tanker in service today meets this definition, from Aframax to VLCC in the tanker size classes. The pre-1982 cohort was phased out under regulation 20, with Category 1 tankers gone by 2005, so the four-limb test now matters mainly when reading an older IOPP certificate or a historical casualty file.
Regulation 33.1 also sets a proving period. The Administration must ensure the system complies fully within one year after the tanker first enters the crude trade, or by the end of its third voyage carrying crude suitable for COW, whichever is later. A newbuilding therefore delivers with a system that is still being proven, and the witnessing of that proof is covered below under the A.897(21) test.
Crude tankers built before June 1982
Older crude tankers reached COW by a different route. Regulation 18.6 required crude tankers of 40,000 dwt and above delivered on or before 1 June 1982 to have segregated ballast tanks (SBT), and regulation 18.7 let them operate crude oil washing under regulations 33 and 35 “in lieu of” SBT, unless they were meant to carry crude unsuitable for washing. Product carriers of the same size and age took the other alternative, dedicated clean ballast tanks under regulation 18.8. COW was therefore the SBT substitute for crude carriers, never a clean-ballast-tank substitute.
Tankers with COW that are not required to have it
Regulation 33.2 reaches ships that fit COW voluntarily. A tanker “not required … to be, but … equipped with crude oil washing equipment” must comply with the safety aspects of the COW Specifications. A crude tanker below 20,000 dwt that chooses to crude wash is bound by the inert gas, oxygen and electrostatic rules in the Specifications, even though regulation 33.1 never required the plant.
Regulation 35 and the Operations and Equipment Manual
Regulation 35 carries the three operating obligations, and none of them sits in regulation 33. Regulation 35.1 requires every oil tanker operating a COW system to carry an Operations and Equipment Manual “to the satisfaction of the Administration”, containing all the information set out in the COW Specifications and revised whenever the system is altered. Regulation 35.2 requires enough tanks to be crude oil washed before each ballast voyage that ballast goes only into washed tanks, taking account of trading pattern and expected weather. Regulation 35.3 requires the system to be operated in accordance with the manual unless the crude is unsuitable for washing.
The standard format of the manual
The manual follows the standard format in MEPC.3(XII), adopted on 30 November 1979 as a recommendation. MEPC.81(43), adopted on 1 July 1999, replaced its section 9 with “Determination of the suitability of a crude oil for use in crude oil washing”, and its preamble names two audiences: the crew, and port State control officers checking the system against its procedures. The COW Operations and Equipment Manual is approved by the flag State or by a recognized organization acting for it.
A.497(XII) requires the manual to state the method for washing each tank, single or multi-stage. In practice the manual also carries:
- the piping and machine arrangement, with a line diagram;
- the shadow diagrams for each tank;
- the minimum supply pressure and the program for each tank;
- the crude grades judged unsuitable for washing;
- the ballasting procedures and the inert gas procedure; and
- the personnel qualifications and the pre-arrival checks.
The COW Specifications and their amendments
The Specifications have a longer history than most IMO guidance. The original text was Resolution 15 of the 1978 International Conference on Tanker Safety and Pollution Prevention. A.446(XI) replaced it in November 1979. A.497(XII), adopted on 19 November 1981, amended the wording on the wedge of crude left on the tank bottom, added the “officer in charge” wording and agreed interpretations on isolation valves, stripping and the small-diameter line. A.897(21), adopted on 25 November 1999, replaced paragraph 4.2.10 only, the effectiveness test.
IOPP Form B cites the set as “resolution A.446(XI) as amended by resolutions A.497(XII) and A.897(21)”, which is the correct citation. A.897(21) is not a revision of the whole Specifications, and it sets no machine throughput, pipe size or pressure. The Specifications have their mandatory force through regulation 33.2, which requires Administration rules to contain “at least all the provisions” of them.
Qualifications of the person in charge
A.446(XI) 5.2 sets a qualification that vetting inspectors check against the crew list. The person in overall charge of COW needs at least one year on oil tankers with duties that included cargo discharge and crude washing, or the training in Appendix II of the Specifications. That person must also have taken part at least twice in COW programs, one of them on the ship concerned or one similar in all relevant respects. Other nominated persons need at least six months on oil tankers in cargo discharge and must be instructed on the particular ship (5.3). The STCW advanced oil tanker training requirement sits on top of these, not in place of them.
Inert gas as the condition for crude oil washing
No tank is crude oil washed unless the inert gas system is working and the tank atmosphere has been measured. The obligation has three layers: SOLAS for the plant, the FSS Code for its performance, and the COW Specifications for the check before each tank.
SOLAS II-2 and FSS Code chapter 15
SOLAS chapter II-2 regulation 4.5.5.1.3, as amended by MSC.365(93) and in force from 1 January 2016, reads: “Tankers operating with a cargo tank cleaning procedure using crude oil washing shall be fitted with an inert gas system complying with the Fire Safety Systems Code and with fixed tank washing machines.” The sentence has no tonnage threshold. The general inert gas requirement in 4.5.5.1.1 and 4.5.5.1.2 applies to tankers of 20,000 dwt and above built from 1 July 2002 and to tankers of 8,000 dwt and above built from 1 January 2016; the COW limb applies regardless of size.
The plant standard is chapter 15 of the FSS Code, revised by MSC.367(93) with effect from 1 January 2016. The marine inert gas system must:
- deliver gas with an oxygen content of not more than 5% by volume at any required flow rate (2.2.1.2.5);
- keep any part of a cargo tank at or below 8% oxygen and at positive pressure, in port and at sea, except when the tank must be gas-free (2.2.1.2.1);
- deliver at least 125% of the ship’s maximum discharge rate (2.2.1.2.4); and
- vent gas automatically when oxygen exceeds 5%, and alarm at a main pressure below 100 mm water gauge (2.2.2.4 and 2.2.4.5.1).
The oxygen check before each tank
A.446(XI) 6.6 sets the measurement that governs every wash. Before each tank is crude oil washed, oxygen is determined “at a point 1 metre from the deck and at the middle region of the ullage space”, and neither reading may exceed 8% by volume. Where a tank has complete or partial wash bulkheads, the readings are taken at similar levels in each section. The oxygen content of the gas being delivered is monitored continuously throughout the wash.
The check is a person with an instrument, not an interlock. Appendix I of the Specifications requires at least one person on deck throughout washing to watch for leaks, test tank oxygen before washing and check tank pressure. The FSS Code requires continuous recording of oxygen and pressure in the inert gas main, not fixed multi-level analyzers inside each tank.
When washing stops
Washing stops under A.446(XI) 6.6 if either condition occurs, and does not resume until conditions are restored:
- the oxygen content of the inert gas being delivered exceeds 8% by volume; or
- the pressure of the atmosphere in the tanks is no longer positive.
Two different oxygen numbers are therefore in play. The 5% figure is the FSS Code plant limit, which triggers automatic venting of the gas. The 8% figure is the tank limit and the COW stop limit. ISGOTT (5th edition, 1.2.3) gives the reason for the 8%: hydrocarbon gas cannot burn below about 11% oxygen by volume, and 8% leaves a margin. ISGOTT 5th edition 7.1.5 also asks that inerted tanks be held at a positive pressure of at least 100 mm water gauge.
Crude oil washing machines and coverage
Only fixed machines may be used for crude oil washing. SOLAS II-2/4.5.5.1.3 requires them on every COW tanker, and ISGOTT 5th edition 11.5.3 states that “only fixed tank washing machines may be used for crude oil washing”. Portable machines lowered through deck openings are for water washing.
Machine types and capacities
A COW machine is a single or twin nozzle unit that turns about two axes on a programmed pattern, driven by the washing fluid through a turbine or by an external drive on deck. Deck-mounted machines must show their rotation and arc externally (A.446(XI) 4.2.12). Submerged bottom machines cannot be seen, so rotation is proved during the discharge by sound or on a ballast passage with water, with checks at intervals set by 4.2.13.
Published manufacturer ranges for machines marketed for crude oil washing, from current datasheets:
| Machine | Flow range | Working pressure | Notes from the datasheet |
|---|---|---|---|
| Scanjet SC 90T2 | 40 to 125 m³/h | 6 to 12 bar | Single nozzle, programmable; 24 mm nozzle gives 61 m³/h and a 33 m jet at 8 bar |
| Alfa Laval Gunclean Toftejorg T-73 | 40 to 93 m³/h | 5 to 12 bar | Marketed for COW on crude carriers, VLCCs and FPSOs; tanks of 5,000 to 30,000 m³ |
| Butterworth K and SK | 6.8 to 79 m³/h | maximum 17.3 bar | Full pattern after 63 axial revolutions |
A single COW machine does not deliver 200 m³/h or more; the published maximum in this set is 125 m³/h. Total washing throughput on a VLCC comes from the number of machines run at once, which is capped by the stripping rule below. The tank washing machine article covers types, drives and maintenance.
Shadow limits
Coverage is regulated by what the jets cannot reach. A.446(XI) 4.2.8 limits the area shielded from direct impingement to 10% of the horizontal areas, meaning the tank bottom and the upper faces of stringers and large primary members, and 15% of the vertical side areas. The manual’s shadow diagrams show the calculation for each tank, and they are the reason machines are placed high and low in deep web-framed tanks.
Supply pressure and stripping capacity
The Specifications set no pressure figure. A.446(XI) 4.3.5 requires the minimum supply pressure to be stated in the manual, and COW is not carried out if it cannot be reached. The COW lines are hydrostatically tested to 1.5 times working pressure (4.1.9), and ISGOTT 5th edition 11.5.5 asks for a pressure test to working pressure before arrival.
Stripping sets the ceiling on how many machines can run on bottoms. Under A.446(XI) 4.4.3 the stripping system must remove oil at 1.25 times the total throughput of all machines operated simultaneously when washing the bottom. A tank being bottom washed faster than it can be stripped floods its own bottom and stops the jets working on the sludge. Stripping pumps and eductors are covered in cargo pumps and piping.
Planning a crude oil washing program
A COW program answers three questions for each discharge: which tanks, in what order, and in how many stages. The answer is fixed by the ballast plan, the sludge rotation and the terminal’s time and vapor limits.
How many tanks to wash
A.446(XI) 6.1 sets the minimum. Before a ballast voyage, enough tanks are crude oil washed to take the departure ballast and any heavy-weather ballast, so that no ballast goes into an unwashed tank. On top of those, “approximately one quarter of all remaining tanks shall be crude oil washed for sludge control on a rotational basis”. The same paragraph adds that “no tank need be crude oil washed more than once in every four months” for sludge control, which caps the requirement rather than setting a minimum frequency.
| Rule | IMO baseline, A.446(XI) 6.1 | United States, 33 CFR 157.160 |
|---|---|---|
| Tanks for ballast | Enough for departure and heavy-weather ballast | Enough for ballast, as in the manual |
| Sludge control | Approximately one quarter of remaining tanks, in rotation | At least 25% of cargo tanks before each ballast voyage |
| Rotation | No tank needs washing more than once in four months | Each tank at least once every fourth discharge from it |
| Upper frequency | Four months | Not more than once in any 120-day period |
| Ballast voyage | No COW during the ballast voyage | No COW during a ballast voyage |
A tanker trading to the United States runs the stricter US rule. The every-fourth-discharge limb has no counterpart in the IMO text.
Top wash, bottom wash and staging
A top wash cleans the upper structure as the cargo level falls, with the washings running down into cargo that is still being discharged. A bottom wash follows once the tank has been drained to the stripping level, and it concentrates on the floor, bottom longitudinals and lower web frames, where sludge collects. A single-stage program runs the full arc from one set-up as the tank empties. A multi-stage program runs the machine through separate arcs at different ullages, with more passes on the bottom. Appendix II of the Specifications lists top washing, bottom washing, trim and recirculatory washing in its training syllabus, and the manual prescribes the method for each tank.
Trim matters because the bottom is drained through the aft suction. Hand dips at the aftermost part of the tank and three other locations establish that the bottom is dry before the wash is signed off (A.446(XI) 4.4.4), and the ORB entry records how it was established.
Dry crude for the wash
The wash oil must be free of settled water. A.446(XI) 6.7 requires the source tank to be discharged by at least 1 metre before its crude is used for washing, which draws off any water that settled on the bottom during the voyage. Any tank used as a slop tank on the previous ballast voyage must be completely discharged and refilled with dry crude before it can supply the wash. ISGOTT 5th edition 11.5.6 gives the reason: crude and water mixtures sprayed through a machine generate electrostatically charged mist well above that of dry crude.
Terminal notice and vapor control
ISGOTT 5th edition 11.5.2 asks the master to inform the terminal and competent authority at least 24 hours before crude oil washing. COW also raises hydrocarbon gas in the tanks “beyond normally existing levels” (ISGOTT 5th edition 11.5.8), which is released when ballast displaces it. ISGOTT lists four ways to avoid releasing it: permanent ballast tanks, ballasting simultaneously with discharge, compressing the gas into other tanks through the inert gas main, or a combination; A.446(XI) 6.8 carries the first two. The VOC management plan required by MARPOL Annex VI regulation 15.6 covers the vapor released, and US ports in ozone non-attainment areas require vapor containment when ballasting cargo tanks under 33 CFR 157.166. Vapor recovery systems are the shore side of the same control.
A tank-cleaning heater outside the engine room is blanked off during crude oil washing (ISGOTT 5th edition 11.5.7), so that crude cannot reach the hot water circuit.
Ballasting crude oil washed tanks
Regulation 35.2 and A.446(XI) 6.1 together decide where departure ballast goes. Ballast is taken only into tanks that have been crude oil washed, and water put into a washed but unrinsed tank “shall be regarded as dirty ballast”. On a double-hull tanker the departure ballast is normally carried in segregated ballast tanks, so the rule bites in heavy weather, when cargo tanks are designated for additional ballast.
Dirty ballast is discharged under the same regime as slop water: through the ODMCS within regulation 34 limits, or to a reception facility. Ballast that must be discharged clean is taken into tanks that have been crude oil washed and then water rinsed, with the rinse water sent to the slop tank.
The ballast and bilge systems article covers the segregated side, which never touches cargo.
Slop tanks and the interface detector
The slop tank is where the tank-cleaning cycle ends up. Everything from water rinses, dirty ballast, line flushing and stripping reaches it, and it has to hold that mixture long enough for oil and water to separate.
Capacity under regulation 29
Regulation 29 requires slop tank arrangements on oil tankers of 150 gross tonnage and above. Regulation 29.2.3 sets a total capacity of not less than 3% of oil carrying capacity, with reductions the Administration “may accept”:
| Arrangement | Minimum slop capacity | Regulation |
|---|---|---|
| General requirement | 3% | 29.2.3 |
| Washing water, once charged, suffices for washing and eductor drive with no water added | 2% | 29.2.3.1 |
| SBT, dedicated clean ballast tanks or a crude oil washing system fitted | 2% | 29.2.3.2 |
| As above, with the no-added-water condition also met | 1.5% | 29.2.3.2 |
| Combination carrier carrying oil only in smooth-walled tanks | 1% | 29.2.3.3 |
| As above, with the no-added-water condition | 0.8% | 29.2.3.3 |
Tankers of 70,000 dwt and above delivered after 31 December 1979 need at least two slop tanks (29.3). The tanks are designed to avoid turbulence and entrainment of oil or emulsion (29.2.4), which is why the inlets and decanting suctions are placed well apart. Where slop tanks carry heating coils, settling can be speeded up on waxy crudes; the cargo tank heating article covers coil arrangements.
Finding the interface
Regulation 32 requires oil tankers of 150 gross tonnage and above to carry approved oil/water interface detectors “for a rapid and accurate determination of the oil/water interface in slop tanks”. Decanting stops at the interface, and the ORB records the ullage of the total contents and of the interface at the start and end of each discharge. Where fixed tank gauging systems report the interface, the approved detector remains the reference for the ORB entry.
Load-on-top and decanting
Load-on-top (LOT) is the procedure that made the slop tank useful. Washings are collected and settled, the water underneath is decanted overboard through the ODMCS within regulation 34 limits, and the next crude cargo is loaded on top of the retained oil. The ICS and OCIMF Clean Seas Guide for Oil Tankers of 1973 records that the Clean Seas program “introduced by the oil and shipping industries in 1964” built in “the now well-known concept of Load on Top”.
The sequence on a ballast passage
- Rinse water, dirty ballast and line flushings are transferred to the slop tank, entering below the liquid surface.
- The contents settle; heating shortens the time on heavy or waxy crudes.
- The officer measures the interface with the regulation 32 detector and records the settling time.
- The ODMCS is started on recirculation, and the overboard valve opens only when the computed rate is within limits and the position, speed and distance-from-land conditions are met.
- Decanting stops before the interface reaches the suction, leaving the oil and the emulsion band on board.
- At the loading port, the terminal is told the slop quantity and quality, and the cargo is loaded on top or the slops are segregated as the charterer instructs.
The retained oil becomes part of the next cargo’s measured quantity. Its declaration, its water content and its effect on outturn are commercial matters that the charter party and the terminal settle, separate from the MARPOL rules.
The regulation 34 conditions
Outside a special area, regulation 34.1 permits discharge of oil or oily mixture from the cargo area only when all of the following hold:
- the tanker is not within a special area;
- it is more than 50 nautical miles from the nearest land;
- it is proceeding en route;
- the instantaneous rate of discharge of oil content does not exceed 30 litres per nautical mile;
- the total quantity discharged does not exceed 1/30,000 of the particular cargo of which the residue formed a part, or 1/15,000 for tankers delivered on or before 31 December 1979; and
- the tanker has an ODMCS and slop tank arrangement in operation as required by regulations 29 and 31.
Inside a special area any discharge from the cargo area is prohibited, except clean or segregated ballast (34.3 and 34.4). The 1/30,000 applies to every oil tanker delivered after 31 December 1979, product carriers included. Regulation 34.8 prohibits chemicals or other substances used to get around the discharge conditions.
Worked example: the total-quantity limit
A VLCC discharges a cargo of 270,000 m³ of crude, and its washings go to the slop tank. The total oil it may discharge from the residue of that cargo is:
$$ Q_{\max} = \frac{270{,}000\ \text{m}^3}{30{,}000} = 9\ \text{m}^3 = 9{,}000\ \text{litres} $$At the maximum instantaneous rate of 30 litres per nautical mile, that allowance is used up in 300 nautical miles of discharge. At 13 knots, 30 litres per nautical mile is 390 litres of oil per hour, so the allowance lasts about 23 hours at the limit. In practice decanting runs well below the rate limit, and the total allowance is rarely the constraint, but the ODMCS computes and records both figures continuously. Once the cumulative figure reaches the limit for that cargo, no further oil from that cargo’s residue may go overboard.
The oil discharge monitoring and control system
Regulation 31 requires oil tankers of 150 gross tonnage and above to carry an ODMCS approved by the Administration, fitted with a recording device that gives a continuous record of discharge in litres per nautical mile and total quantity, or oil content and rate. The record must be identifiable by time and date and kept for at least three years. Any failure stops the discharge.
Specification and recording
The equipment standard depends on the keel date. MEPC.108(49), adopted on 18 July 2003, applies to oil tankers with keels laid on or after 1 January 2005; earlier installations were approved to A.586(14) or earlier resolutions, and IOPP Form B item 6.1 records which. Under MEPC.108(49):
- the oil content meter’s full scale is not less than 1,000 ppm (6.2.6);
- a starting interlock prevents the discharge valve opening before the system is fully operational (3.4);
- the record carries instantaneous rate, oil content, total quantity, time and date in UTC, speed, position, effluent flow, overboard valve status, oil type setting, alarms, failures and overrides (6.9.2); and
- data are recorded at start and stop, at intervals of not more than 10 minutes during discharge, on alarm, and whenever the computed rate changes by 10 litres per nautical mile (6.9.3).
The printout or electronic record is retained for at least three years (6.9.1). There is no “12-month” retention figure in the instrument.
MEPC.240(65), adopted on 17 May 2013, amends the specifications for tankers built from 1 January 2005. It is a recommendation to Administrations when approving equipment, with no entry-into-force date, and it extends the approval to each biofuel blend containing 75% or more petroleum oil carried under MEPC.1/Circ.761. It also sets the manual alternative on failure: locate the interface with the regulation 32 detector, observe the water surface beside the discharge, and record everything in ORB Part II sections H and I.
When the ODMCS fails
Regulation 31.2 is specific. The discharge stops; a manually operated alternative method may be used; the defective unit is made operable as soon as possible; and “subject to allowance by the port State authority” the tanker may make one ballast voyage before going to a repair port. The failure is entered in ORB Part II under regulation 36.6, code M, with the time of failure, the time restored and the reason. Regulation 31 imposes no separate report to the flag State; company procedures and some flags add one.
The ODMCS is often confused with the 15 ppm equipment in the engine room. The machinery-space regime is regulation 14 and regulation 15, with oily water separators and a 15 ppm alarm and automatic stop on ships of 10,000 GT and above. The cargo-area ODMCS works to 30 litres per nautical mile and the cargo-based total, not to 15 ppm.
Water washing
Water washing follows crude oil washing when a tank has to take clean ballast, be inspected, receive a different grade, or be entered for repair. It uses sea water, cold or heated, through fixed machines or portable machines on hoses, and it sends everything to the slop tank.
Washing in an inert atmosphere
Water washing an inerted tank follows the same atmosphere rules as COW: oxygen at or below 8% and positive pressure throughout (ISGOTT 5th edition 7.1.6). The main risk is operational, not static. Wash water carries oil into the slop tank and must be settled before decanting.
Washing in a non-inert atmosphere
Where a tank’s oxygen has not been confirmed below 8%, ISGOTT treats it as non-inert and replaces atmosphere control with fuel and ignition control. ISGOTT 5th edition 11.3.5.2 sets the limits:
| Control | Limit |
|---|---|
| Before washing | Tank ventilated to 10% LFL or less, tested at several levels |
| During washing | Stop if 35% LFL is reached at any location; resume at 10% LFL or less |
| Machine throughput | Not more than 60 m³/h per machine |
| Tank throughput | Not more than 180 m³/h per tank |
| Recirculated wash water | Not permitted |
| Chemical additives | Only with wash water at or below 60 °C |
| Steam | Never injected |
| Metallic sounding equipment | Only via a full-depth sounding pipe, or bonded and earthed, during washing and for 5 hours after (1 hour if continuously mechanically ventilated) |
The bottom and lines are flushed with water and stripped before washing starts, without using the machines. Portable machine hoses are made up and tested for electrical continuity before the machine goes into the tank, with resistance not above 6 ohms per metre length (11.3.6.3), and the machine is suspended by natural fiber rope, not by its hose.
Hot water, chemicals and steam
Hot water washing is normal for waxy residues. The machine datasheets cap operating temperature (95 °C for both the SC 90T2 and the T-73). In a non-inert tank, ISGOTT 5th edition 11.3.5.2 requires increased monitoring above 60 °C and limits chemical additives to wash water at or below 60 °C. Tank cleaning chemicals capable of producing a flammable atmosphere are used only in inerted tanks, with the safety data sheet on board (11.3.6.8).
Steaming is restricted to tanks that are inerted, or water washed and gas freed with flammable gas not above 10% LFL before steaming starts (11.3.6.8). Steam jets are strong charge generators, which is why the non-inert washing rules ban them outright.
Grade changes on product tankers
Product carriers clean between grades rather than for sludge. A move from a dirty to a clean grade, or to a grade with a tight color or flash-point specification, needs water washing, sometimes with chemicals, followed by gas-freeing and a visual or wall-wash check. Grade-change tank cleaning is a separate practice with its own charter-party time and cost clauses.
Static electricity during tank washing
Static is the ignition source that tank-washing rules are built around. ISGOTT 5th edition 3.3.4 explains the mechanism: water washing produces a charged mist, recirculation or chemical additives can raise the potential sharply, and corona discharges in the mist are not incendive. The ignition route is a discharge to an unearthed conductor introduced into the tank, or a slug of water thrown by a high-capacity single-nozzle fixed machine.
That mechanism sets the practical rules:
- in a non-inert tank, nothing metallic goes in unless it is bonded and earthed or through a full-depth sounding pipe, for five hours after washing or one hour with continuous mechanical ventilation (11.3.5.2(g));
- metal sounding rods on earthed metal tapes are allowed in that period, and metal rods on fiber rope or synthetic rope are not;
- portable washing machines are bonded to their hoses and the hoses tested for continuity (11.3.6.1 and 11.3.6.3);
- portable fans are non-sparking, bonded to the deck and water, hydraulic, pneumatic or steam driven, with no steam exhausted into the tank (11.4.6); and
- crude for washing is dry crude, because wet crude mists charge more (11.5.6).
The five-hour and one-hour figures are a non-inert water-washing rule. They are not a crude oil washing rule and there is no “three-hour” figure in ISGOTT. The 30-minute waiting period in ISGOTT 5th edition 11.1.7 belongs to loading static accumulator oils. Static electricity on tankers covers the full ISGOTT chapter.
The NTSB investigated a static ignition in tank-cleaning preparation on the tank barge IB1940 at Lemont, Illinois, on 4 November 2019 (NTSB/MAB-20/34, issued 29 September 2020). The probable cause was an unbonded air mover operated in a tank with residual acetone, which produced a static discharge that ignited the vapor. The barge was an inland US unit, not a seagoing crude tanker, but the failure was the bonding rule in ISGOTT 11.4.6.
Purging and gas-freeing
A crude oil washed tank is inerted and hydrocarbon rich. Getting it to a state where people can enter takes two steps in a fixed order: purge with inert gas, then gas-free with air.
Purging to 2% hydrocarbon
ISGOTT 5th edition 7.1.6.10 requires the tank to be purged with inert gas “to reduce the hydrocarbon content to 2% or less by volume” before air is introduced, so that during gas-freeing “no portion of the tank atmosphere is brought within the flammable range”. Crude oil vapor has lower and upper flammable limits of roughly 1% and 10% by volume for general purposes (ISGOTT 5th edition 1.2.2), so the 2% end-point is above the LFL. It is a purge target chosen so that dilution with air never crosses the flammable envelope, not a gas-free condition.
Two methods are used. Dilution runs the inert gas plant at full capacity to produce turbulence and mix the tank. Displacement introduces inert gas at low velocity to push the hydrocarbon out as a layer. The gas-freeing and purging article covers the choice of method and the vent arrangement.
Instruments for inerted tanks
A catalytic (pellistor) flammable gas indicator needs at least 11% oxygen, and ISGOTT 5th edition 2.4.3 states it should not be used to measure hydrocarbon in an inert atmosphere. Purge end-points are taken with an instrument designed for oxygen-deficient atmospheres, such as an infrared analyzer, which “does not require the presence of air” (2.4.6.2). Catalytic and electrochemical gas sensors and their bump testing and calibration are covered separately. SOLAS regulation XI-1/7, added by MSC.380(94) and in force from 1 July 2016, requires every ship to which chapter I applies to carry portable instruments that measure oxygen, flammable gas, hydrogen sulfide and carbon monoxide before enclosed space entry.
The gas-free condition
The FSS Code chapter 15, 2.1.4, defines gas-free as hydrocarbon or other flammable vapor below 1% of the lower flammable limit, oxygen at least 21%, and no toxic gases present. ISGOTT 5th edition 7.1.6.12 asks for a steady oxygen reading of 21% and not more than 1% LFL, with toxic gases below their exposure limits, and 11.4.4 allows about 10 minutes for readings to stabilize. Fixed gas-freeing fans are not used on a system ventilating another tank that is being washed (11.4.5).
Gas-free is the precondition for entry, not for hot work. Entry proceeds under the enclosed space entry permit and the confined space entry and tank inspection procedure, which covers the IMO entry recommendations and the IACS Recommendation 72 limits. Hot work needs its own permit and stricter criteria (ISGOTT 5th edition 11.4.8).
Preparing for survey and dry dock
Tanks are washed and gas freed before any internal survey. Oil tankers of 500 gross tonnage and above are surveyed under SOLAS regulation XI-1/2 and the 2011 ESP Code, A.1049(27), mandatory from 1 January 2014 through MSC.325(90). The ESP scope covers cargo tanks, pump rooms, cofferdams, pipe tunnels, voids in the cargo area and all ballast tanks, and it applies from delivery, not from a given age. Close-up surveys and thickness measurement need clean, gas-free, lit tanks, so the washing program before a special survey is heavier than a routine one.
Category 2 and 3 tankers of 15 years and over also fall under the Condition Assessment Scheme, MEPC.94(46), through regulation 20.6. Category 1 tankers were phased out in 2005 and are not in the scheme’s current scope.
Hydrogen sulfide, benzene and pyrophoric iron sulfide
Sour crude and light crude bring toxic hazards into every stage of tank cleaning. The governing exposure limit is the one set by the flag State or national authority and adopted in the company safety management system under the ISM Code; ISGOTT and the IMO entry recommendations point to those limits rather than setting their own.
Hydrogen sulfide
Hydrogen sulfide gives no reliable warning by smell. ISGOTT 5th edition Table 2.1 places first detection by smell at 0.1 to 0.5 ppm, the sense of smell starting to break down at 50 to 100 ppm, and loss of smell within 2 to 5 minutes at 150 ppm. The same edition records a crude with 70 ppm by weight of H2S producing 7,000 ppm by volume at the vent (2.3.6.2). The current ACGIH values are a TLV-TWA of 1 ppm and a STEL of 5 ppm; ISGOTT 5th edition, published in 2006, gave 5 ppm TWA. After sour crude, ISGOTT asks that no work be done on deck without respiratory protection where more than 5 ppm is present (7.1.7.1).
Benzene
Benzene is the controlling toxic in light crude and gasoline-range cargoes, and its odor threshold is well above its exposure limit. ACGIH reduced its TLV-TWA to 0.02 ppm in January 2024 and removed the STEL; the previous values of 0.5 ppm TWA and 2.5 ppm STEL dated from 1997. ISGOTT 5th edition 2.3.5.2 cites IMO’s 1 ppm TWA. Tanks that carried benzene-bearing cargo are tested for benzene before entry, whichever limit the company applies; benzene on tankers covers the monitoring.
Pyrophoric iron sulfide
Iron sulfide forms on tank steel where hydrogen sulfide is present and oxygen is lacking, and it oxidizes fast enough to glow when air reaches it. ISGOTT 5th edition 2.6 states there is “no safe level of hydrogen sulphide below which a pyrophor cannot be generated”, that inerted crude carriers carry the higher risk, and that “as long as the cargo tanks remain inerted, there is no danger of ignition”. The defense is procedural: keep tanks inerted through the voyage and any ballast discharge, and do not discharge with the inert gas plant down. Pyrophoric iron sulfide has its own article.
Oil Record Book Part II entries
Cargo, washing and slop operations are recorded in Oil Record Book Part II, not Part I. Regulation 36 requires Part II on every oil tanker of 150 gross tonnage and above, covering cargo and ballast operations. Part I, under regulation 17, covers machinery space operations on oil tankers of 150 GT and above and other ships of 400 GT and above.
The codes in Appendix III to Annex I, with section J as replaced by MEPC.187(59) in force from 1 January 2011:
| Code | Operation |
|---|---|
| A | Loading of oil cargo |
| B | Internal transfer of oil cargo during voyage |
| C | Unloading of oil cargo |
| D | Crude oil washing (COW tankers only) |
| E | Ballasting of cargo tanks |
| F | Ballasting of dedicated clean ballast tanks (CBT tankers only) |
| G | Cleaning of cargo tanks |
| H | Discharge of dirty ballast |
| I | Discharge of water from slop tanks into the sea |
| J | Collection, transfer and disposal of residues and oily mixtures not otherwise dealt with |
| K | Discharge of clean ballast contained in cargo tanks |
| L | Discharge of ballast from dedicated clean ballast tanks (CBT tankers only) |
| M | Condition of the oil discharge monitoring and control system |
| N | Accidental or other exceptional discharges of oil |
| O | Additional operational procedures and general remarks |
The five codes that carry tank cleaning have fixed items. Code D records the port or position, the tanks washed, the number of machines, start and finish times, the washing pattern (single or multi-stage, vertical arc and the number of times covered), the washing line pressure, the method of establishing that the tank was dry, and the reasons where the manual’s program was not followed. Code G records the tanks, the duration and the method: hand hosing, machine washing or chemical cleaning, with the chemical and amount, and whether the washings went to slop tanks or a reception facility. Codes H and I record whether the ODMCS was in operation; code I adds the settling time, the ullage of the total contents and of the interface at start and finish, and the ship’s speed. Code M records ODMCS failures.
Each operation is signed by the officer in charge and each page by the master (36.5); the book is kept for three years after the last entry (36.7). Since 1 October 2020, MEPC.314(74) has allowed an Administration-approved electronic record book in place of the paper Part II.
Port State control officers compare code D, G, H and I entries against the ODMCS printout, the inert gas recorder and the slop tank ullages under the operational requirements of regulation 11. Vetting inspections under SIRE ask the same questions for charterers. A code D entry that does not match the manual’s program has to explain the difference in its remarks line.
Proving a COW installation: the A.897(21) test
A COW system is proved in service before it is accepted. Paragraph 4.2.10 of the Specifications, as replaced by A.897(21), requires the Administration to witness crude oil washing and to check, for at least one tank of each group, the supply pressure, the cycle times and the machine operation. After final draining, hand dips are taken forward, center and aft and recorded in the manual.
For ships whose washed cargo tanks may take ballast, the test has two quantitative limbs:
- oil on the departure ballast must not exceed 0.00085 of the ballast volume, by visual or measured assessment; and
- the arrival ballast is discharged through an approved oil discharge monitor at not more than 15 ppm, or sampled for shore laboratory analysis.
Internal visual inspection is not mandatory, and video is accepted. The results feed IOPP certificate Form B, items 5.4, which record the COW system and its specification. Where a classification society carries out statutory work for the flag as its recognized organization, the witnessing falls within that delegation.
Regional overlays
The IMO text is the baseline everywhere. Two regional regimes change what a crude tanker does in practice.
United States: 33 CFR Part 157
33 CFR Part 157 carries its own COW rules in subpart D (157.100 to 157.172). The ship scope matches regulation 33, crude tankers of 20,000 dwt and above that are new by the June 1982 definition (157.10(e)), and the differences are operational:
- 157.160 sets the numerical tank rule: at least 25% of cargo tanks washed before each ballast voyage, each tank at least every fourth discharge, and no tank more than once in 120 days;
- 157.164 repeats the 1 metre and mid-ullage oxygen readings at 8% and adds that a crew member monitors the inert gas instruments unless there is an 8% alarm in the cargo control room;
- 157.155 requires the source tank to be lowered by at least one metre, and rotation of bottom machines to be verified;
- 157.168 requires a crew member with COW monitoring duty on deck throughout; and
- 157.118 bars a foreign tanker within its scope from entering US navigable waters or transferring cargo without a COW manual approved by the Coast Guard or by the flag to the IMO standard.
The US discharge rule in 157.37 matches regulation 34 on rate, distance and total quantity, and it covers cargo pump room bilges as well as cargo and slop tanks. MARPOL is given effect in US law by the Act to Prevent Pollution from Ships, 33 U.S.C. 1901 et seq., which is a separate statute from the Oil Pollution Act of 1990.
European Union: Directive (EU) 2019/883
The EU port reception facilities directive, Directive (EU) 2019/883 of 17 April 2019, repealed Directive 2000/59/EC and had to be transposed by 28 June 2021. Its definition of cargo residues includes residues “entrained in wash-water” (Art 2(5)). Article 7 requires a ship to deliver its waste before leaving an EU port unless it has enough dedicated storage to reach the next port, which is the test a tanker retaining slops under load-on-top must meet. Advance waste notification is due 24 hours before arrival (Art 6).
The directive’s cost-recovery system under Article 8(1) covers waste “other than cargo residues”, so tank washings and slops are charged outside the indirect fee, under each Member State’s arrangements. Crude-loading terminals worldwide carry a parallel MARPOL obligation under regulation 38.2.1: reception facilities for tankers arriving after a ballast voyage of not more than 72 hours or 1,200 nautical miles.
Commercial consequences: outturn, ROB and time
Crude oil washing is paid for in discharge time and returned in delivered cargo. The ICS and OCIMF Clean Seas Guide of 1973 put the residue left after discharge in the water-washing era at about 0.2 to 0.5% of the cargo carried. On a 280,000-tonne cargo that range is 560 to 1,400 tonnes; COW puts a large part of it back into the delivered cargo, and what stays on board is measured as cargo remaining on board (ROB).
Three commercial effects follow:
- Outturn claims. A shortage claim turns on whether the ROB is liquid and pumpable, and the evidence is the code D entries, the method used to establish that each tank was dry, and the independent surveyor’s ullage report.
- Laytime. Washing extends discharge. How the extra time counts against laytime is set by the charter party’s crude oil washing wording, and the time actually taken is argued from the COW log and the pumping record, which is why the code D start and finish times matter.
- Slop disposition. Under load-on-top the retained slops are declared at the next loading port, and the charterer either takes them as part of the cargo or has them kept segregated.
Charterers and their vetting departments review the same records through SIRE inspections, and INTERTANKO and OCIMF represent the owner and oil-company sides of that relationship.
Tank condition also matters to cargo tank coatings and to the owner’s position on asphaltene sludge left by incompatible crudes. Heavy sludge that COW cannot move is removed by hand in dry dock, after entry criteria are met (ISGOTT 5th edition 11.3.6.10).
Limitations
- ISGOTT edition. The ISGOTT figures on this page are cited from the 5th edition (2006) with its section numbers. The 6th edition (2020) is current and moved the material to section 12.3 (tank cleaning), 12.4 (gas freeing), 12.5 (crude oil washing) and chapter 3 (static electricity). Check each figure against the current edition and the company SMS before relying on it operationally.
- Exposure limits differ by flag State and national authority. The ACGIH and ISGOTT values given here are references, not the limit a given ship must apply.
- Machine data are manufacturer ranges for named models, not a statement of what a given ship has fitted. The ship’s manual governs pressures, programs and cycle times.
- Terminal rules. Terminals and ports add their own conditions on COW, vapor release and slop delivery, which this article does not list.
- Regional coverage is limited to the IMO baseline, the United States and the European Union. China, Singapore, Australia and other port-State rules on COW and slops are not covered here.
- Amendments. The page reflects the Annex I, SOLAS and FSS Code texts in force on its last-modified date. An amendment adopted after that date is not reflected here until the page is revised.
- Commercial terms depend on the charter party wording. The outturn and laytime points describe the usual structure, not the effect of a particular clause.
Frequently Asked Questions (FAQs)
What is crude oil washing?
Crude oil washing (COW) is the cleaning of an oil tanker’s cargo tanks with the crude oil cargo itself, sprayed through fixed tank washing machines while the cargo is being discharged.
The crude dissolves waxy and asphaltic deposits and carries them ashore with the cargo. It is governed by MARPOL Annex I regulations 33 and 35 and by the COW Specifications, IMO Resolution A.446(XI) as amended by A.497(XII) and A.897(21).
Which tankers must be fitted with a crude oil washing system?
Every crude oil tanker of 20,000 tonnes deadweight and above delivered after 1 June 1982, as defined in MARPOL Annex I regulation 1.28.4, under regulation 33.1.
The definition is met by any one of: a building contract placed after 1 June 1979, a keel laid after 1 January 1980, delivery after 1 June 1982, or a major conversion on the same dates.
Does a product tanker have to crude oil wash?
No. Regulation 33.1 applies to crude oil tankers, defined in regulation 1 as oil tankers engaged in the trade of carrying crude oil.
A product tanker is not required to fit COW. Where any tanker is equipped with COW without being required to, regulation 33.2 still binds it to the safety aspects of the COW Specifications.
How long does a new crude tanker have to prove its COW system?
Regulation 33.1 requires the Administration to ensure full compliance within one year after the tanker first enters the crude oil trade, or by the end of its third voyage carrying crude suitable for crude oil washing, whichever occurs later.
Where is the COW Operations and Equipment Manual required?
In MARPOL Annex I regulation 35.1, not regulation 33.
Every oil tanker operating a COW system must carry a manual approved by the Administration that details the system and specifies the operating procedures, containing all the information the COW Specifications set out. The standard format is MEPC.3(XII) of 30 November 1979, with section 9 replaced by MEPC.81(43) of 1 July 1999.
What oxygen level is required before a tank is crude oil washed?
The oxygen content must not exceed 8% by volume at either of two points: 1 metre below the deck and the middle of the ullage space.
Where a tank has wash bulkheads, the readings are taken at those levels in each section. The rule is paragraph 6.6 of the COW Specifications, A.446(XI), repeated in ISGOTT 5th edition 7.1.6.9 and in 33 CFR 157.164 for the United States.
When must crude oil washing stop?
Under A.446(XI) 6.6, washing stops if the oxygen content of the inert gas being delivered exceeds 8% by volume, or if the pressure of the atmosphere in the tanks is no longer positive.
It resumes only when satisfactory conditions are restored. The minimum supply pressure in the manual is a second stop condition: if it cannot be reached, COW is not carried out (4.3.5).
Can a small crude tanker run COW without inert gas?
No. SOLAS II-2/4.5.5.1.3, as amended by MSC.365(93) with effect from 1 January 2016, requires any tanker operating a cargo tank cleaning procedure using crude oil washing to be fitted with an inert gas system complying with the FSS Code and with fixed tank washing machines.
The sentence carries no tonnage threshold.
Can portable machines be used for crude oil washing?
No. ISGOTT (5th edition, 11.5.3) states that only fixed tank washing machines may be used for crude oil washing, and SOLAS II-2/4.5.5.1.3 requires fixed machines on any COW tanker.
Portable machines are used for water washing.
How many tanks have to be crude oil washed at each discharge?
Enough to take the departure and heavy-weather ballast in washed tanks, plus approximately one quarter of the remaining tanks for sludge control on a rotational basis: A.446(XI) 6.1.
No tank need be washed for sludge control more than once in every four months. The US rule in 33 CFR 157.160 is numerical: at least 25% of cargo tanks before each ballast voyage and each tank at least every fourth discharge, but not more than once in 120 days.
Is the four-month figure a minimum washing frequency?
No. A.446(XI) 6.1 says no tank need be crude oil washed for sludge control more than once in every four months.
It caps how often washing is required; it does not require a tank to be washed at least every four months.
Can crude oil washing be done on the ballast voyage?
No. A.446(XI) 6.1 states that no crude oil washing shall be undertaken during the ballast voyage.
All COW is completed before the tanker leaves its final discharge port, and 33 CFR 157.160(a)(4) carries the same prohibition for US-regulated tankers.
What is dry crude and why must it be used for washing?
Dry crude is crude oil from which free water has been removed by settling.
A.446(XI) 6.7 requires the source tank to be discharged by at least 1 metre before its oil is used for washing, and any tank used as a slop tank on the previous ballast voyage to be completely discharged and refilled with dry crude first. Crude and water mixtures generate charged mist well above that of dry crude (ISGOTT 5th edition 11.5.6).
Is ballast in a crude oil washed tank clean ballast?
No. A.446(XI) 6.1 states that water put into a tank that has been crude oil washed but not water rinsed is dirty ballast.
It can only be discharged under regulation 34, through the ODMCS, or delivered to a reception facility.
What stripping capacity does a COW system need?
The stripping system must remove oil at 1.25 times the total throughput of all tank cleaning machines operated simultaneously when washing tank bottoms: A.446(XI) 4.4.3, with the A.497(XII) interpretation applying it to any stage of bottom washing.
How much of a tank may be shadowed from the washing jets?
Under A.446(XI) 4.2.8 the area shielded from direct jet impingement must not exceed 10% of the horizontal areas (tank bottom and upper faces of stringers and large primary members) and 15% of the vertical side areas.
The shadow diagram in the manual demonstrates it.
Who may be in charge of crude oil washing?
A.446(XI) 5.2 requires the person in overall charge to have at least one year on oil tankers with duties including cargo discharge and crude washing, or equivalent training, and to have taken part at least twice in COW programs, one on the ship concerned or a ship similar in all relevant respects.
Other nominated persons need at least six months on oil tankers (5.3).
What is the minimum pressure for crude oil washing?
The COW Specifications do not state a figure.
A.446(XI) 4.3.5 requires the minimum supply pressure to be specified in the Operations and Equipment Manual, and COW is not carried out if that pressure cannot be obtained.
How much slop tank capacity must a COW tanker have?
Regulation 29.2.3 sets not less than 3% of oil carrying capacity.
The Administration may accept 2% where a crude oil washing system is fitted, and 1.5% where the washing water, once charged, is sufficient without adding more water. Tankers of 70,000 dwt and above delivered after 31 December 1979 must have at least two slop tanks (29.3).
What is load-on-top?
Load-on-top (LOT) is the practice of collecting tank washings and dirty ballast in a slop tank, letting oil and water separate by gravity, decanting the water layer overboard through the ODMCS within regulation 34 limits, and loading the next crude cargo on top of the retained oil.
The ICS and OCIMF Clean Seas Guide of 1973 records it as part of the Clean Seas program the oil and shipping industries introduced in 1964.
What are the regulation 34 discharge conditions for tank washings?
Outside a special area, all of: more than 50 nautical miles from the nearest land, proceeding en route, instantaneous rate of oil discharge not above 30 litres per nautical mile, total oil discharged not above 1/30,000 of the particular cargo of which the residue formed a part (1/15,000 for tankers delivered on or before 31 December 1979), and an operating ODMCS and slop tank arrangement.
Inside a special area, discharge from the cargo area is prohibited except clean or segregated ballast.
Does the 1/30,000 limit apply only to crude oil tankers?
No.
Regulation 34.1.5 applies 1/30,000 to every oil tanker delivered after 31 December 1979, crude or product, and 1/15,000 to tankers delivered on or before that date.
How long must ODMCS records be kept?
At least three years. Regulation 31.2 requires the record to be identifiable by time and date and kept for three years, and MEPC.108(49) 6.9.1 requires the printout or electronic record to be retained for the same period.
During discharge the system records at intervals of not more than 10 minutes (6.9.3).
What happens if the ODMCS fails during decanting?
The discharge stops (regulation 31.2). A manually operated alternative method may be used, and the defective unit must be repaired as soon as possible.
Subject to allowance by the port State authority, the tanker may make one ballast voyage before going to a repair port. The failure is recorded in Oil Record Book Part II, code M, under regulation 36.6.
Where is crude oil washing recorded in the Oil Record Book?
In Oil Record Book Part II (cargo and ballast operations), required by regulation 36 for oil tankers of 150 gross tonnage and above.
Crude oil washing is code D, cleaning of cargo tanks is code G, discharge of dirty ballast is code H, and discharge of water from slop tanks is code I. Part I, under regulation 17, covers machinery space operations only.
Does the Oil Record Book have a field for the pre-wash oxygen reading?
No. The code D entry in Appendix III covers port or position, tanks washed, number of machines, start and finish times, washing pattern, washing line pressure, the method of establishing that the tank was dry, and remarks.
Oxygen readings are required by A.446(XI) 6.6 and are recorded under the manual’s procedures, not in a code D item.
What are the non-inert water washing limits in ISGOTT?
In ISGOTT 5th edition 11.3.5.2: ventilate to 10% of the lower flammable limit or less before washing, stop at 35% LFL, not more than 60 m3/h per machine and 180 m3/h per tank, no recirculated wash water, chemical additives only with wash water at or below 60 °C, and no steam injection.
Why can a normal explosimeter not be used when purging a cargo tank?
A catalytic (pellistor) flammable gas indicator needs at least 11% oxygen to read correctly, so it cannot measure hydrocarbon in an inerted tank (ISGOTT 5th edition 2.4.3).
Purge end-points are measured with an instrument designed for oxygen-deficient atmospheres, such as an infrared analyzer.
What is the purge end-point before gas-freeing?
Hydrocarbon content reduced to 2% or less by volume with inert gas, so that no part of the tank atmosphere passes through the flammable range when air is introduced (ISGOTT 5th edition 7.1.6.10).
The 2% figure is above the roughly 1% LFL, and is a purge target, not a gas-free condition.
When is a cargo tank gas-free?
The FSS Code chapter 15, 2.1.4, as revised by MSC.367(93), defines gas-free as hydrocarbon or other flammable vapor below 1% of the lower flammable limit, oxygen at least 21% and no toxic gases present.
ISGOTT asks for steady readings. Entry is then made under the enclosed space entry procedure; hot work needs further criteria.
How long after water washing can a metal sounding rod be used?
In a non-inert tank, ISGOTT 5th edition 11.3.5.2(g) allows metallic sounding equipment only through a full-depth sounding pipe or when bonded and earthed, during washing and for five hours afterward.
If the tank is continuously mechanically ventilated after washing, the period falls to one hour.
Can steam be used to clean an oil cargo tank?
Only in a tank that is inerted, or water washed and gas freed with flammable gas not above 10% LFL before steaming (ISGOTT 5th edition 11.3.6.8).
Steam is never injected during non-inert washing, because steam jets generate static charge.
What is pyrophoric iron sulfide and why does it matter after sour crude?
Iron sulfide forms on tank steel where hydrogen sulfide is present and oxygen is absent.
When exposed to air it oxidizes fast enough to glow and can ignite a flammable atmosphere. ISGOTT (5th edition 2.6) states there is no safe level of H2S below which it cannot form, and the defense is keeping tanks inerted until they are washed and gas freed.
What H2S and benzene limits apply during tank cleaning?
The occupational exposure limit set by the flag State or national authority, applied through the company safety management system.
For reference, the ACGIH TLV-TWA for hydrogen sulfide is 1 ppm with a 5 ppm STEL, and for benzene 0.02 ppm since January 2024. ISGOTT 5th edition (2006) gave 5 ppm TWA for H2S and cited IMO’s 1 ppm TWA for benzene.
Can hydrogen sulfide be detected by smell during tank cleaning?
Not reliably. ISGOTT 5th edition Table 2.1 puts first detection at 0.1 to 0.5 ppm, the sense of smell starting to fail at 50 to 100 ppm, and loss of smell within 2 to 5 minutes at 150 ppm.
Personal and portable detectors are the control.
How much notice is given to a terminal before crude oil washing?
ISGOTT 5th edition 11.5.2 asks the master to inform the competent authority and the terminal at least 24 hours in advance.
How is a COW system proved effective at approval?
Under A.446(XI) 4.2.10 as replaced by A.897(21), the Administration witnesses crude oil washing, monitoring supply pressure, cycle times and machine function, and hand dips are taken forward, center and aft after final draining.
For ships whose washed tanks take ballast, oil on departure ballast must not exceed 0.00085 of the ballast volume, and arrival ballast discharged through the ODM must not exceed 15 ppm.
Why does a US port require a COW manual from a foreign tanker?
33 CFR 157.118 bars a foreign tank vessel within its scope from entering US navigable waters or transferring cargo unless it carries a COW manual approved by the US Coast Guard or approved by the flag state to the IMO standard, with the matching certificate or letter of acceptance.
Do EU ports charge for delivering tank washings?
Directive (EU) 2019/883 requires ships to deliver waste to port reception facilities before leaving an EU port unless they have enough dedicated storage to the next port.
Its indirect-fee system under Article 8(1) covers waste other than cargo residues, so tank washings and slops are charged outside that fee under national arrangements.
How much cargo does crude oil washing recover?
No single figure applies to every crude and trade.
The ICS and OCIMF Clean Seas Guide of 1973 put residue remaining after discharge in the water-washing era at about 0.2 to 0.5% of the cargo carried, which sets the scale of what COW returns into the cargo stream. Measured recovery depends on the crude’s wax and asphaltene content, the program run and the tank condition.
No question matches. Try a shorter or different word.
Sources
- IMO Resolution MEPC.117(52), revised MARPOL Annex I, adopted 15 October 2004. regulations 1.28, 18, 29 to 36 and Appendix III (Oil Record Book Part II) imo.org
- IMO Resolution A.446(XI), Revised Specifications for the Design, Operation and Control of Crude Oil Washing Systems, adopted 15 November 1979. 4.2.8, 4.3.5, 4.4.3, 5.2, 6.1, 6.6 and 6.7 imo.org
- IMO Resolution A.497(XII), amendments to the COW Specifications, adopted 19 November 1981 imo.org
- IMO Resolution A.897(21), amendments to paragraph 4.2.10 of the COW Specifications, adopted 25 November 1999 imo.org
- IMO Resolution MEPC.3(XII), Standard Format of the Crude Oil Washing Operations and Equipment Manual, adopted 30 November 1979 imo.org
- IMO Resolution MEPC.81(43), amendments to Section 9 of the Standard Format for the COW Manual, adopted 1 July 1999 imo.org
- IMO Resolution MEPC.108(49), Revised Guidelines and Specifications for Oil Discharge Monitoring and Control Systems for Oil Tankers, adopted 18 July 2003. 6.9 recording imo.org
- IMO Resolution MEPC.240(65), 2013 amendments to the ODMCS Guidelines and Specifications, adopted 17 May 2013 imo.org
- IMO Resolution MEPC.187(59), amendments to MARPOL Annex I including Oil Record Book Part II section J, adopted 17 July 2009 imo.org
- IMO Resolution MSC.365(93), amendments to SOLAS chapter II-2 including regulation 4.5.5.1.3, adopted 22 May 2014 imo.org
- IMO Resolution MSC.367(93), revised FSS Code chapter 15 inert gas systems, adopted 22 May 2014. 2.1.4, 2.2.1.2 and 2.2.4.5 imo.org
- 33 CFR Part 157, tank vessels carrying oil in bulk. 157.10, 157.37, 157.118, 157.155, 157.160 and 157.164 ecfr.gov
- ISGOTT, International Safety Guide for Oil Tankers and Terminals, 5th edition (2006), ICS, OCIMF and IAPH, reference copy. 1.2, 2.3, 2.4, 2.6, 7.1.6, 11.3, 11.4 and 11.5 slcprdwordpressstorage.blob.core.windows.net
- ICS and OCIMF, Clean Seas Guide for Oil Tankers, 1973. load on top and residue after discharge archive.org
- NTSB Marine Accident Brief NTSB/MAB-20/34, explosion aboard barge IB1940, Lemont, Illinois, 4 November 2019 ntsb.gov
- Scanjet SC 90T2 tank cleaning machine datasheet scanjet.net
- Alfa Laval Gunclean Toftejorg T-73 product leaflet alfalaval.com
- ACGIH, benzene TLV-TWA 0.02 ppm acgih.org